Products
Ultrasonic measurement Time-of-Flight Prosonic FMU41
0 out of 5 based on 0 customer ratings
(0 customer reviews)
Product Meta
Category: Level Measurement
Tag: Endress+Hauser
Product Description
-
Measuring principle
Ultrasonic
-
Characteristic / Application
Compact ultrasonic transmitter
-
Supply / Communication
2-wire HART
-
Accuracy
+/- 2 mm or +/- 0,2 % of set measuring range
-
Ambient temperature
-40 °C … 80 °C
(-40 °F … 176 °F) -
Process temperature
-40 °C … 80 °C
(-40 °F … 176 °F) -
Process pressure / max. overpressure limit
0.7 bar … 3 bar abs
(10 psi … 44 psi) -
Main wetted parts
PVDF
-
Process connection
G / NPT 2″
-
Blocking distance
0.35 m (1.15 ft)
-
Max. measurement distance
Liquids: 8 m (26 ft),
Solids: 3.5 m (11 ft) -
Communication
4…20 mA HART
-
Certificates / Approvals
ATEX, FM, CSA, TIIS, INMETRO, NEPSI
-
Application limits
For higher resistance:
FMU42/FDU9x
Foam / high turbulence possible:
FMU42/FDU91
Fast filling and discharging rate:
FMU90 + FDU9x
Level limit detection:
FMU90 + FDU9x
Be the first to review “Ultrasonic measurement Time-of-Flight Prosonic FMU41” Cancel reply
Reviews
There are no reviews yet.